ADC PowerWorx Power Distribution User Manual

Page 38

Advertising
background image

ADCP-80-575 • Issue 2 • December 2006

Page 32
© 2006, ADC Telecommunications, Inc.

* Unless otherwise specifically permitted in the code, as defined in the NEC document cited
(ANSI/NEC 70), the overcurrent protection for conductor types marked with an asterisk (*)
shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10
copper, after any correction factors for ambient temperature and number of conductors have
been applied.

500

320

380

430

600

355

420

475

700

385

460

520

750

400

335

380

800

410

490

555

900

435

520

585

1000

455

545

615

1250

495

590

665

1500

520

625

705

1750

545

650

735

2000

560

665

750

CORRECTION FACTORS

For ambient temperatures other than 30C (86F), multiply

the allowable ampacities shown by the appropriate factor shown below.

21-25

1.08

1.05

1.04

26-30

1.00

1.00

1.00

31-35

.91

.94

.96

36-40

.82

.88

.91

41-45

.71

.82

.87

46-50

.58

.75

.82

51-55

.41

.67

.76

56-60

....

.58

.71

61-70

....

.33

.58

71-80

....

....

.41

Table 310-16 (NEC): Allowable Ampacities of Insulated Conductors, Rated O Through 2000 Volts, 60

° to

90

°C (140° to 194°F), Not More Than Three Current-Carrying Conductors in Raceway or Cable or Earth

(Directly Buried), Based on Ambient Temperature of 30

°C (86°F)

SIZE

TEMPERATURE RATING OF CONDUCTOR

AWG

KCMIL

60

°C

(114

°F)

60

°C

(114

°F)

60

°C

(114

°F)

TYPES

TW*,

UF*

TYPES

FEPW*,

RH*, RHW*,

THHW*,

THW*,

THWN*,
XHHW*,

USE*, ZW*

TYPES

TBS, SA,

SIS, FEP*,

FEPB*, MI,

RHH*, RHW-2,

THHN*,

THHW*, THW-2*,

THWN-2*,

USE-2,

XHH,

XHHW*

XHHW-2

ZW-2

Advertising