Appendix a: shield connector installation – ADC FPL Series User Manual

Page 33

Advertising
background image

ADCP-90-328 • Issue 2 • November 2005

Page 33

© 2005, ADC Telecommunications, Inc.

APPENDIX A: SHIELD CONNECTOR INSTALLATION

This appendix provides the procedures for installing Scotchlok 4460 Shield Connectors, which
are manufactured by the 3M Company and utilized in the Fiber Management Panel. The shield
connector kit provides a means for grounding cables that have a metallic shield. Use the
following procedure to install each kit:

1. The shield connector kit is comprised of the components shown in

Figure 34

.

Figure 34. Kit Components

2. Prepare the cable by cutting the shield flush with the outer cable sheath as shown in

Figure 35

.

If the cable has a double sheath, cut only the outer sheath and shield leaving the inner sheath
intact as shown.

Figure 35. Cable Preparation

2 SECURING NUTS

TOP

BASE

9172-A

CORE

WRAP

CABLE

SHEATH

.75 IN. (19 mm)

SINGLE SHEATH CABLE

DOUBLE SHEATH CABLE

DOUBLE SHEATH CABLE

.75 IN. (19 mm)

OUTER

SHEATH

INNER

SHEATH

CORE

WRAP

0.13 IN

(3mm)

9173-A

Advertising