Refrigerator installation – LG LSC27914ST User Manual

Page 10

Advertising
background image

10

CONNECTING THE WATER LINE

NOTE: Water line installation is needed when the

Automatic Icemaker and/or Water Dispenser

features are available on your product.

BEFORE YOU BEGIN

This water line installation is not warranted by the

refrigerator or icemaker manufacturer or seller.

Follow these instructions carefully to minimize the risk

of expensive water damage.

Water hammer (water banging in the pipes) in house

plumbing can cause damage to refrigerator parts

and lead to water leakage or flooding. Call a qualified

plumber to correct water hammer before installing the

water supply line to the refrigerator.

To prevent burns and product damage, do not hook up

the water line to the hot water line.

If you use your refrigerator before connecting the water

line, make sure the icemaker power switch is in the

OFF

(O) position.

Do not install the icemaker tubing in areas where

temperatures fall below freezing.

When using any electrical device (such as a power drill)

during installation, be sure the device is double

insulated or grounded in a manner to prevent the

hazard of electric shock, or is battery-powered.

All installations MUST be in accordance with local

plumbing code requirements.

NOTE: Wear eye protection.

• If a reverse osmosis water filtration system is

connected to your cold water supply, the water line

installation is not warranted by the refrigerator or

icemaker manufacturer or seller. Follow next

instruction carefully to minimize the risk of expensive

water damage.

• If a reverse osmosis water filtration system is

connected to your cold water supply, the water

pressure to the reverse osmosis system needs to be

a minimum of 40 to 60 PSI (2,8 kg•f/cm² ~ 4,2 kg•f/

cm² , less than 2~3 sec to fill a cup of 7 oz. capacity).

If the water pressure from the reverse osmosis system

is less than 21 PSI (1,5 kg•f/cm², more than 4 sec to

fill a cup of 7 oz. capacity):

• Check to see whether the sediment filter in the

reverse osmosis system is blocked. Replace the filter

if necessary.

• Allow the storage tank on the reverse osmosis system

to refill after heavy usage.

• If the issue about water pressure from reverse

osmosis remains, call a licensed, qualified plumber.

WHAT YOU WILL NEED

• Copper Tubing, 1/4” (6,35 mm) outer diameter to

connect the refrigerator to the water

supply. Be sure both ends of the

tubing are cut square.

To determine how much tubing you need, measure the

distance from the water valve on the back of the

refrigerator to the water supply pipe. Then add 8 feet

(2,4 m). Be sure there is sufficient extra tubing (about

8 feet [2,4 m] coiled into 3 turns of about 10” [25 cm]

diameter) to allow the refrigerator to move out from the

wall after installation.

Be sure that the kit you select allows at least 8 feet

(2,4 m) as described above.

• A cold water supply. The water pressure MUST be

between 20 and 120 PSI (1,4 bar and 8,2 bar) on

models without a water filter and between 40 and 120

PSI (2,8 bar and 8,2 bar) on models with a water filter.

• Power drill.

• 1/2” (12,7 mm) or

Adjustable Wrench.

• Flat head and Phillips screwdrivers.

• Two 1/4” (6,35 mm) outer diameter compression nuts

and 2 ferrules (sleeves) to

connect the copper tubing to

the shutoff valve and the

refrigerator water valve.

• If your existing copper water line has a flared fitting at

the end, you will need an

adapter (available at

plumbing supply stores) to

connect the water line to the

refrigerator OR you can cut off the

flared fitting with a tube cutter and

then use a compression fitting.

• Shutoff valve to connect to the cold water line.

The shutoff valve should have a water inlet with a

minimum inside diameter of

5/32”(3,96 mm) at the point

of connection to the COLD

WATER LINE. Saddle-type

shutoff valves are included in

many water supply kits. Before

purchasing, make sure a saddle-type valve complies

with your local plumbing codes.

INSTALLATION INSTRUCTIONS

WARNING:

Connect to potable water supply only.

1. SHUTOFF THE MAIN WATER SUPPLY

Turn on the nearest faucet to relieve the pressure on

the line.

2. CHOOSE THE VALVE LOCATION

Choose a location for the valve that is easily

accessible. It is best to connect into

the side of a vertical water pipe. When

it is necessary to connect into a

horizontal water pipe, make the

connection to the top or side, rather

than at the bottom, to avoid drawing

off any sediment from the water pipe.

REFRIGERATOR INSTALLATION

Advertising
This manual is related to the following products: