Moving the rack requires a clear, uncarpeted pathway that is at least 80 cm (31.5 in) wide for
the 60.3 cm (23.7 in) wide, 42U rack. A vertical clearance of 203.2 cm (80 in) should ensure
sufficient clearance for the 200 cm (78.7 in) high, 42U rack.

CAUTION:

Ensure that no vertical or horizontal restrictions exist that would prevent rack movement

without damaging the rack.

Make sure that all four leveler feet are in the fully raised position. This process will ensure that the
casters support the rack weight and the feet do not impede movement.

Each rack requires an area 600 mm (23.62 in) wide and 1000 mm (39.37 in) deep (see

Figure 30 (page 57)

).

Figure 30 Single rack configuration floor space requirements

2. Rear door

1. Front door

4. Service area width 813 mm

3. Rack width 600 mm

6. Rack depth 1000 mm

5. Rear service area depth 300 mm

8. Total rack depth 1706 mm

7. Front service area depth 406 mm

If the feet are not fully raised, complete the following procedure:
1.

Raise one foot by turning the leveler foot hex nut counterclockwise until the weight of the rack
is fully on the caster (see

Figure 31 (page 58)

).

2.

Repeat

Step 1

for the other feet.