En.01 noncritical condition—blower speed, En.02 critical condition—blower speed, En.03 unrecoverable condition—blower failure – HP 4000.6000.8000 Enterprise Virtual Arrays User Manual

Page 122: En.04 unrecoverable condition—blower internal, En.05 noncritical condition—blower missing

Advertising
background image

Figure 41 Blower element numbering

CAUTION:

A single

blower

operating at high speed can provide sufficient air flow to cool an

enclosure and the elements for up to 100 hours. However, operating an enclosure at temperatures
approaching an overheating threshold can damage elements and may reduce the MTBF of a
specific element. Immediate replacement of the defective blower is required.

The following sections define the power supply condition reports.

0.3.en.01 NONCRITICAL condition—Blower speed

A

blower

is operating at a speed outside of the EMU specified range, possibly because of a

bearing problem. This can affect enclosure cooling and cause an element to fail. This condition
report remains active until the problem is corrected.
This error does not normally require immediate correction. However, an error of this type could
contribute to an element overheating.
HP recommends replacing the

blower

as soon as possible.

To correct this problem, record all six characters of the condition report, then contact your HP
authorized service representative.

0.3.en.02 CRITICAL condition—Blower speed

A

blower

is operating at a speed that is significantly outside the EMU specified range, possibly

because of a bearing problem. This can cause the loss of cooling and cause an element to fail.
The error remains active until the problem is corrected.
HP recommends replacing the

blower

as soon as possible.

To correct this problem, record all six characters of the condition report, then contact your authorized
service representative.

0.3.en.03 UNRECOVERABLE condition—Blower failure

A

blower

has stopped. The operational blower now operates at high speed and is a single point

of failure. This condition report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your authorized
service representative.

0.3.en.04 UNRECOVERABLE condition—Blower internal

A power supply reported an internal

blower

error that could affect enclosure cooling and cause

an element to fail. HP recommends correcting the problem before the blower fails. This condition
report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP
authorized service representative.

0.3.en.05 NONCRITICAL condition—Blower missing

A

blower

has been removed or is improperly installed. Even though the blower flaps close to

maintain the proper air flow, the reduced cooling capability can cause overheating, causing an
element to fail. This condition report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP
authorized service representative.

122

EMU-generated condition reports