Component identification 21

The only two valid fan configurations are listed in the following table.

Configuration

Fan bay 1 Fan bay 2 Fan bay 3 Fan bay 4 Fan bay 5 Fan bay 6

1 processor

Fan

Fan

Fan

Fan

Fan blank

Fan blank

2 processors

Fan

Fan

Fan

Fan

Fan

Fan

For a single-processor configuration, four fans and two blanks are required in specific fan bays for

redundancy. A fan failure or missing fan causes all fans to spin at high speed. A second fan failure or missing

fan causes an orderly shutdown of the server.
Installing more than the required number of fans in a single-processor configuration is not a supported

configuration.
For a dual-processor configuration, six fans are required for redundancy. A fan failure or missing fan causes

all fans to spin at high speed. A second fan failure or missing fan causes an orderly shutdown of the server.
The server supports variable fan speeds. The fans operate at minimum speed until a temperature change

requires a fan speed increase to cool the server. The server shuts down during the following

temperature-related scenarios:

At POST and in the OS, iLO 2 performs an orderly shutdown if a cautionary temperature level is
detected. If the server hardware detects a critical temperature level before an orderly shutdown occurs,

the server performs an immediate shutdown.

When the Thermal Shutdown feature is disabled in RBSU, iLO 2 does not perform an orderly shutdown
when a cautionary temperature level is detected. Disabling this feature does not disable the server

hardware from performing an immediate shutdown when a critical temperature level is detected.

CAUTION:

A thermal event can damage server components when the Thermal Shutdown feature

is disabled in RBSU.