Installation 13

3.

If you are connecting through the virtual serial port with the provided USB cable, then you must
download and install the USB driver, available from the HP website (

http://www.hp.com

).

4.

Using the USB cable provided, connect a PC to the USB port on the management module.

5.

If your Windows operating system does not prompt you to install a driver, you must install it manually
through the device manager and locate the downloaded driver.

6.

Access the management module through a terminal emulation program, such as Minicom or
HyperTerminal ("

Configuring HyperTerminal

" on page

41

).

7.

Confirm that you have set the following parameters to access a terminal emulation program:

o

Bits per second: 9600

o

Data bits: 8

o

Parity: none

o

Stop bits: 1

o

Flow control: none

8.

Log in to the HP Modular Cooling System Configuration Utility:

a.

In the login field, enter the user name. The default user name is Admin.

b.

In the password field, enter the password. The default password is Admin. The Main Menu screen
appears.

9.

Enter the product ID and serial number on the 1 Network Configuration line. The product ID and

10-digit serial number are located on a label inside the rear MCS-100 unit door.