Overview menu – HP Modular Cooling System Options User Manual

Page 9

Advertising
background image

Web interface 9

Overview menu

To display the Overview screen, in the left navigation frame, click Overview. This screen displays graphic

meters for temperature and cooling system parameters.

Parameter

Function

Server Intake Temperature

Displays the average server intake temperature

Server Exhaust Temperature Displays the average server exhaust temperature
Cooling

Displays the heat removed by the water

Water Inlet Temperature

Displays the temperature of the water coming into the
MCS 5042 unit to be used to cool the servers

Water Outlet Temperature

Displays the temperature of the water after removing

the server heat

Water Flow

Displays the water flow rate in liters or gallons per

minute

Water Valve

Displays the percentage of the water valve opening

Water System Integrity

Displays the Leak Detected Alarm, the Condensation

Pump Warning, and condensation pump activity

Cycles—Displays the number of times the pump

runs

Duration—Displays the total amount of time the

pump has run since it was last activated

Fan Speed Target

Displays the fan speed level from 0 to 100%.

0%= Fan turned off

100%= Fan at maximum speed

Cooling Module 1, 2, and 3 Displays the Server Intake and Server Exhaust

temperatures and fan speeds

Magnetic Door Lock Status

Displays the door lock status

OKThe door lock is functioning properly and the

doors are closed.

Doors ReleasedEither the front or back door is

open.

AC Input 1 and 2

Displays the health of the power supply

Dew point monitoring

Displays humidity level inside the rack cabinet,

calculated dew point, and rack door status