Environmental requirements and specifications

Site wiring must include an earth ground connection to the DC power source. Grounding must comply

with local, national, or other applicable government codes and regulations.

Power circuits and associated circuit breakers must provide sufficient power and overload protection.

Weight and placement guidelines

Refer to

"Physical requirements" (page 77)

for detailed size and weight specifications.

The weight of an enclosure depends on the number and type of modules installed.

Ideally, use two people to lift an enclosure. However, one person can safely lift an enclosure if its

weight is reduced by removing the power supply modules and disk drive modules.

Do not place enclosures in a vertical position. Always install and operate the enclosures in a

horizontal/level orientation.

When installing enclosures in a rack, make sure that any surfaces over which you might move the rack

can support the weight. To prevent accidents when moving equipment, especially on sloped loading

docks and up ramps to raised floors, ensure you have a sufficient number of helpers. Remove obstacles

such as cables and other objects from the floor.

To prevent the rack from tipping, and to minimize personnel injury in the event of a seismic occurrence,

securely anchor the rack to a wall or other rigid structure that is attached to both the floor and to the

ceiling of the room.

Electrical guidelines

These enclosures work with single-phase power systems having an earth ground connection. To reduce

the risk of electric shock, do not plug an enclosure into any other type of power system. Contact your

facilities manager or a qualified electrician if you are not sure what type of power is supplied to your

building.

Enclosures are shipped with a grounding-type (three-wire) power cord. To reduce the risk of electric

shock, always plug the cord into a grounded power outlet.

Do not use household extension cords with the enclosures. Not all power cords have the same current

ratings. Household extension cords do not have overload protection and are not meant for use with

computer systems.

Ventilation requirements

Refer to

"Environmental requirements" (page 78)

for detailed environmental requirements.

Do not block or cover ventilation openings at the front and rear of an enclosure. Never place an

enclosure near a radiator or heating vent. Failure to follow these guidelines can cause overheating and

affect the reliability and warranty of your enclosure.

Leave a minimum of 15 cm (6 inches) at the front and back of each enclosure to ensure adequate

airflow for cooling. No cooling clearance is required on the sides, top, or bottom of enclosures.

Leave enough space in front and in back of an enclosure to allow access to enclosure components for

servicing. Removing a component requires a clearance of at least 37 cm (15 inches) in front of and

behind the enclosure.

Cabling requirements

Keep power and interface cables clear of foot traffic. Route cables in locations that protect the cables

from damage.

Route interface cables away from motors and other sources of magnetic or radio frequency

interference.

Stay within the cable length limitations.

Management host requirements

A local management host with at least one USB Type B port connection is recommended for the initial

installation and configuration of a controller enclosure. After you configure one or both of the controller