Installation examples, Cont'd) – Amana HRV-300D User Manual

Page 17

Advertising
background image

17

Bedrooms

Fresh Air

Exhaust Air

Furnace thermostat

Exhaust

Bathroom

460 mm

HRV

Central Control - optional

Return Air

HRV
Connection

1800

mm

INSTALLATION EXAMPLES

(CONT'D)

Example diagram only-duct configuration may change depending on model

Partially Dedicated System

Stale air drawn from key areas of
home (bathroom, kitchen, laundry)

Fresh air supplied to main living
areas via the forced air system.

HRV must be balanced

DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN
(Stale air drawn from key areas of home)

Exhaust Air from various parts of home.
i.e. bathrooms (if required),
kitchens (if required)

NOTES:

1.Furnace blower may be required to operate when HRV/ERV is on to provide good air distribution.
2.Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended.

18” (460mm) above grade minimum.

3.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HRV/ERV’s airflow must be

confirmed on site, using the balancing procedure found in the installation manual.

* Unit is normally balanced on HIGH speed with furnace blower ON.

Outdoors

Return Air

1 m

(3’-3”) min.

recommended

Cool Air

Return

* Ducts connection may
vary depending on model