Setup & Commissioning (continued)

Light level
The light level feature allows lighting to
remain OFF during daylight, regardless of
occupancy. Daytime operation is at 200
footcandles (factory setting). Nighttime
operation is at .2 footcandles.
The adjusting screw turned fully clockwise
means daylight operation at approx. 200
fc (factory setting). Turning fully counter-
clockwise means nighttime operation at
.2 fc. When adjusting the detection zone
and for the performance test in daylight,
the adjusting screw must be turned fully
clockwise.

Time delay
Time delay is the period of time lights
remain on after the last detection.
Adjustment ranges from 30 sec (factory
setting) to 30 min.
The adjusting screw turned fully counter-
clockwise means the shortest time and
fully clockwise means the longest. The

time delay is restarted by any movement
detected before this time elapses. The
shortest time setting is recommended
when adjusting the detection zone and for
the performance test.
Note: Every time the light switches off, it
takes approximately two seconds for the
sensor to start detecting movement again.

Reach/sensitivity
The sensor’s reach setting can be
adjusted. Turning the adjustment screw
fully counter-clockwise selects minimum
reach (about 3.3 feet) and fully clockwise
selects maximum reach (about 26 feet).

7

www.steinel.net

(800) 852-4343

Time delay: 30 seconds
to 30 minutes

Sensitivity: adjusts coverage
reach from approx 3.3 feet
to 26 feet

Light level: .2 (night) to 200
(day) footcandles