INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND T3CDS & T3CDSPB

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

www.cmp-products.com

CABLE GLAND COMPONENTS

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION

1. Separate the gland into two sub-assemblies, A and B, by unscrewing the body (2) from the entry

item (1). Note that items (4) and (5) are loose items.

2. Prepare the cable by stripping back the

cable outer sheath and armour to suit the

equipment geometry. Expose the armour

by stripping back the outer sheath further

using the table below as a guide.

3. Secure the entry components (sub-assembly A) into the equipment. (Not for remote installation)

Pass the sub-assembly B (outer seal first) and AnyWay clamping ring (5) over the cable.

Insert the reversible armour cone (4) in the sub-assembly A, orientation to suit cable (see below)

4. Pass the cable through sub-assembly A, spacing the armour or braid evenly around the cone.

Whilst continuing to push the cable forward to keep the cable braid or armour in contact with the

cone, tighten the compensating sleeve (3) into the entry component (1) until all the threads are

used. (Note that the internal compensator will prevent the cable gland inner seal from being over-

tightened onto the cable inner sheath.)

The inner sheath of the T3CDSPB gland contains a device to automatically make an electrical

contact with the lead sheath on the cable as the cable is installed.

5. Terminate the cable by tightening the body (2) onto the entry component (1) using a spanner on

each part. Tighten the body until the body and entry components are metal to metal and cannot

be tightened further.

6. Tighten the outer seal nut (6) until it comes to an effective stop. This will occur when:-

A) The outer seal nut (6) has clearly engaged the cable and cannot be further tightened

without the use of excessive force by the installer.

B) The outer seal nut (6) is metal to metal with the body of the gland (2).

4

3

2

1

1.

Entry Item

2.

Body

3.

Compensating Sleeve

4.

Reversible Armour Cone

5.

AnyWay Clamping Ring

6.

Outer Seal Nut

6

5

SUB-ASSEMBLY A

ITEM 4

ITEM 5

SUB-ASSEMBLY B

“CDS” INNER SEAL

HOUSING

DELUGE

SEAL

REVERSIBLE

ARMOUR CONE

ANYWAY

CLAMPING RING

BODY AND OUTER

SEAL NUT

CABLE GLAND SIZE

20S/16, 20S, 20

25S, 25, 32, 40

50S, 50, 63S, 63 75S, 75, 90, 100, 115, 130

CABLE STRIP LENGTH “L”

12mm

15mm

18mm

20mm

Cable Strip

Length “L”

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

Grooved side of

cone outwards -

to terminate braid,

strip armour, pliable

wire or tape armour.

Stepped side of

cone outwards -

to terminate SWA

cable.