Routing the fiber patch cord – ADC DL3XR-FCA100 User Manual

Page 18

Advertising
background image

Installing a D3LX CO Module in an LEC

LTPS-UM-8013-03

10

August 30, 2002

D3LX CO and RMT Modules

Figure 5.

Routing the Fiber Patch Cord

4

Locate the mounting slots designated for the D3LX CO modules in the chassis.

5

Refer to

Figure 6 on page 11

for D3LX CO module locations chassis and slot corresponding to the DS3

signal.

If no protection switching is required, proceed to the next step.

If protection switching is required, a working module may be installed in the first slot of any quad group,
such as 1-1, 2-1, 3-1, 4-1, 5-1, 6-1, or 7-1. The protection module is installed in the slot to its immediate
right in the order of 1-3, 2-3, 3-3, 4-3, 5-3, 6-3, or 7-3. For more information on protection switching,
refer to

“Protection Switching” on page 4

.

Install the working module first, then the protect module.

FiberGuide vertical duct

Heat baffle/fiber management panel

Fiber patch cord