Applica 130A Heaters User Manual

Page 11

Advertising
background image

Installation

Page 11

E

LECTRICAL

C

ONNECTIONS

Be sure that electrical service to the heater has proper

overload fuse or circuit breaker protection, wire size and con-
nections which comply with all applicable codes.

NOTE: If it is necessary to replace any of the origi-
nal wiring, use 105°C wire or its equivalent, and/or
150°C wire or its equivalent, like the original wiring.
See Figures 18 and 19 for wire ratings.

M

ILLIVOLT

H

EATERS

The Millivolt models are equipped with a self-generating

electrical system in which the electrical current is provided by
a pilot generator. No external electrical connections are
required.

When installing a remote switch, do not exceed 10 ft of

wiring from the heater. Use 18-gauge stranded wire.

E

LECTRONIC

H

EATERS

NOTE: Electronic heaters come standard with a
120 VAC 3-prong power cord. For 240 VAC applica-
tions, see instructions below. Power source must be
a wired ground, with ground fault circuit interruption
circuitry.

Figure 16. Electronic Heater Power.

The Direct Spark Ignition Device automatically lights the

main burners upon a call for heat. The heater is supplied with
a dual voltage transformer for 120/240 VAC input power
hookup.

Heater must be electrically grounded and bonded in

accordance with local codes, or, in the absence of local
codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70. (Canada - Canadian Electrical Code, CSA
C22.1, Part 1 and Part 2.)

NOTE: Input power to the heater (120 VAC) can be
supplied from the load (pump) side of time clock or
directly from the GFCI power source. It is preferred
to make connection to the load/pump side of the
time clock.

WARNING

RISK OF ELECTRICAL SHOCK. MORE THAN ONE DIS-
CONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE
THE EQUIPMENT BEFORE SERVICING.