Disconnect messages, Troubleshooting – Outback Power Systems GS3548E Operators Manual User Manual

Page 62

Advertising
background image

Troubleshooting

60

900-0145-01-01 Rev A

Disconnect Messages

Disconnect messages explain why the inverter has disconnected from an AC source after previously

being connected. The unit returns to inverting mode if turned on.

This screen is viewed using the AC

INPUT

hot key on the MATE3. One or more messages will display Y (yes). If a message says N (no), it

is not the cause of the disconnection. The MATE3 system display may generate a concurrent event

and warning message following the disconnection. (See page 58.) If the AC source is removed, the

warning will be blank, but the cause of the last disconnection will remain.

Disconnect messages only display the reason for the disconnection; they cannot correct it. It is usually
the result of external conditions, not an inverter fault. If the condition is corrected, the inverter will

reconnect. A few settings can be changed to accommodate problems with the AC source.
The reasons shown in the Sell Status menu for ceasing to sell power (see next page) may be the same

as disconnect messages. If the Grid Interface Protection settings are exceeded (see page 12), the

inverter will disconnect from the utility grid.
Table 10

shows the primary seven reasons for disconnection. An eighth field may be visible, but it can

feature several different messages which vary with conditions. A list of these messages and their

definitions is featured on the OutBack website at www.outbackpower.com.

Table 10

Disconnect Troubleshooting

Message

Definition

Possible Remedy

Frequency Too High The AC source has exceeded acceptable

frequency levels.

Check AC source. If it is a generator, reduce speed.

Frequency Too Low

The AC source has dropped below

acceptable frequency levels.

Check AC source. If it is a generator, increase speed.

Voltage > Maximum The AC source has exceeded acceptable

voltage levels.

Check AC source. The inverter’s acceptance range is

adjustable.
NOTE: Adjusting the range may accommodate a

problematic AC source, but it will not fix it.

Voltage < Minimum

The AC source has dropped below

acceptable voltage levels.

Check AC source. The inverter’s acceptance range is

adjustable.
NOTE: Adjusting the range may accommodate a
problematic AC source, but it will not fix it.

Backfeed

Usually indicates that another AC power

source (out of phase with the inverter) was

connected to the AC output.
Can also occur if an out-of-phase AC source

is connected to the AC input.

Disconnect the AC OUT wires. Check the wires (not

the inverter) with an AC voltmeter. If an AC source is

present, shut it off. (This is more often accompanied

by an

AC Output Backfeed error.)

Check input source and wiring. This can be caused by

a source with phase problems

Phase Lock

The unit cannot remain in phase with an
erratic AC source.

Check AC source. This can be caused by a generator
with a poorly regulated output. Some generators

perform this way when low on fuel. If necessary, use

the

Generator input mode. (See page 13.)

Island Detect

The grid seems to be present but normal

grid conditions are not detected. This can

occur if the Radian’s input is powered by

another inverter instead of the grid. It may

be the result of an open main disconnect.

Check all input disconnects or circuit breakers for an

open circuit. Check for any other inverters installed in

the system and disable them.
This may (rarely) occur with a generator. If necessary,

use the

Generator input mode. (See page 13.)

Advertising
This manual is related to the following products: