System error codes and troubleshooting – AMX Distribution Matrix Octaire User Manual

Page 68

Advertising
background image

Octaire Control Panel Operation

64

Octaire Instruction Manual

System Error Codes and Troubleshooting

This section provides an overview of the most common error codes that may appear on an Octaire
Control Panel. The table below lists the error code, the name of the code, the meaning of the code, and
some basic troubleshooting strategies (additional troubleshooting strategies are included on page 65).
The codes in the table are not intended to be comprehensive. If an error code appears that is not listed,
note the specific number and contact technical support (see page 31).

The first letter of the error code indicates the following:

E = Error

W = Warning

A = Alarm* (requires immediate attention)

I = Information*

* Because these codes very rarely appear, they are not included in the table.

For the following instructions, use HyperTerminal on an external controller (see page 25).

To enable error code reporting:

1.

Enter $ERR=1!
System responds with V

Note: If the power is cycled, you will need to enable error code reporting again.

To turn off error code reporting:

1.

Enter $ERR=0!

Most Common System Error Codes

Error Codes

Name

Meaning

Troubleshooting Strategies

E01000A

Enclosure
timeout error

One or more of the enclosures
in a multi-enclosure system did
not acknowledge a control
operation command.

• Resend the command.

• Check the Status LED on the rear of each

enclosure. If any are red, contact
Technical Support.

• Check the power indicators.

• Check the link connections between

enclosures.

EFF8002

Enclosure
timeout error

The operation was not
completed before the timer
expired.

• Resend the command.

• Check the power indicators.

• Check the link connections in

multi-enclosure systems.

• Check that the command was sent using

the correct routing level (All, Video or
Audio).

E01DFFF

Audio
request error

A volume or gain request was
made on the Video routing level.

• Resend the command on All or Audio.

W010005

Sync timeout
warning

The system did not receive the
vertical interval sync signal.
Note that the switch occurred,
but not at the sync interval.

• Resend the command.

• Check the sync cable connections.

• Check the Control Panel to verify that sync

is enabled (see page 61).

• Check that the sync signal from the

generator is being received by the system.