Armstrong World Industries ACUM185 User Manual

Page 27

Advertising
background image

AR-EXP-CUMMINS-07-00

OWNERS MANUAL

Page 27

after the Safety On timer has expired, a shutdown is initi-
ated. The icon will flash.


NOTE:- The

icon is used to indicate both underspeed

and overspeed. A flashing icon indicates underspeed. A
steady icon indicates overspeed.

7.2. SETTINGS


7.2.1 FIXED SETTINGS
The following settings are factory set and are NOT adjust-
able.
























7.3 TERMINAL DESCRIPTION

NOTE:- All the outputs are solid state, rated at 1.2
Amps 8 Volts to 35 Volts DC, and switch to battery
negative when active.

Crank disconnect

20Hz

Underspeed

20Hz

Overspeed

57Hz (50Hz nominal)
68 Hz (60Hz nominal)

Remote start delay

5s

Preheat

10s

Crank period

10s

Crank rest

10s

Safety delay

10s

Remote stop delay

30s

PIN
No

DESCRIP-
TION

CABLE SIZE NOTES

1

DC Plant Sup-
ply Input (-ve)

1.0mm

Connected to
plant battery
negative

2

DC Plant Sup-
ply Input (+ve)

1.0mm

Connected to
plant battery
positive
(Recommende
d Fuse 2A)

3

Fuel relay Out-
put

0.5mm

Used to oper-
ate the fuel
solenoid con-
trol relay.

4

Start relay
Output

0.5mm

Used to oper-
ate the crank-
ing control
relay.

5

Preheat Out-
put relay

0.5mm

Used to oper-
ate the pre-
heat control
relay.

6

Remote Start
Input

0.5mm

Switch to
negative to
start set.

7

Charge Fail
Input/ Excita-
tion Output

1.0mm

Must NOT be
connected to
plant supply
negative if not
used.

8

Low Oil Pres-
sure Input

0.5mm

Switch to
negative on
fault.

9

High Engine
Temp Input

0.5mm

Switch to
negative on
fault.