Configure module 5 - cooling parameters (5-o2) 44 – Red Lion TCU User Manual

Page 52

Advertising
background image

Configure Module 5 - Cooling Parameters (5-O2)

Unit returns to configuration access point if cooling option is not installed.

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

CYC2

Cooling output cycle
time

0 to 250 sec
(2)

0 turns OP2 off.

GAN2

Relative cooling
gain

0.0 to 10.0
(1.0)

0.0 places cooling
output into ON/OFF
control mode and
db-2 becomes
hysteresis value.

db-2

Heating/cooling
overlap-deadband

-999 to 9999
(0)

Positive value is
deadband. Negative
value is overlap. If
GAN2 = 0, this
parameter is cooling
ON/OFF control
hysteresis.