Configure module 5 - cooling parameters (5-o2) 44 – Red Lion TCU User Manual
Page 52
Advertising
Configure Module 5 - Cooling Parameters (5-O2)
Unit returns to configuration access point if cooling option is not installed.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
CYC2
Cooling output cycle
time
0 to 250 sec
(2)
0 turns OP2 off.
GAN2
Relative cooling
gain
0.0 to 10.0
(1.0)
0.0 places cooling
output into ON/OFF
control mode and
db-2 becomes
hysteresis value.
db-2
Heating/cooling
overlap-deadband
-999 to 9999
(0)
Positive value is
deadband. Negative
value is overlap. If
GAN2 = 0, this
parameter is cooling
ON/OFF control
hysteresis.