Operating and Installation Instructions

CONA

®

-control

8.0 Troubleshooting

In the event of a malfunction or faulty operating performance, check that all installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If you cannot correct the fault with the help of the table in section "9.0 Troubleshooting
table
", please consult the supplier or manufacturer.

9.0 Troubleshooting table

9.1 Fault indications on the measuring amplifier

ATTENTION !
- Read sections 10.0 and 1
1.0 prior to all dismantling or repair work!
- Read section 6.0 before
restarting the plant!

Fault

Possible cause

Corrective measure

power LED not lit

Mains voltage failure

Check the mains power supply

Operating voltage is incorrect

Connect the operating voltage
indicated on the rating plate

Electronics have burnt out

Make sure the mains voltage
coincides with the value indicated
on the rating plate.
Replace the electronics

Terminal not connected correctly or
cable does not make proper contact
inside terminal

Insert the terminal securely and
check the connecting cable

Indication Meaning

Possible cause

Corrective measure

Blockage

Sensor surrounded by
cold condensate and /
or condensate
temperature is below
specified value

Detection temperature is too high

Set a lower detection temperature
(refer to 4.4 Measuring amplifier)

Depending on the steam trap type /
plant operating conditions,
condensate may collect in the test
chamber after the plant has been
shut down

No fault
The plant / part of the plant is not in
operation

High accumulation of condensate,
with the result that the capacity of
the steam trap is no longer
adequate

Select a steam trip with a higher
capacity

If thermal steam traps are installed,
the sub-cooling temperature is too
high

Refer to the Operating Instructions
for the steam trap

Blocked strainer or valve inside the
steam trap
Defective controller inside the
steam trap

Leakage

Steam leakage
Sensor surrounded by
steam and
temperature is above
specified value

Dirt has got inside the steam trap
control element, with the result that
the valve no longer closes

Check the steam trap
Refer to the Operating Instructions
for the steam trap

Controller defective

Blockage
+
Leakage

Sensor surrounded by
cold air / steam

Plant / steam trap not in operation

No fault
The plant / part of the plant is not in
operation