5 settings, 1 torque switch off – ARI Armaturen ARI-PACO 1,6kN EN User Manual

Page 14

Advertising
background image

Page 14

0040506001 1811

Operating and installation instructions

Electric thrust actuator ARI-PACO 1,6 kN

5.4.3.1 ARI-PACO 1,6 D
- Connect the ground line of the connection lead to connector 1 of the connection strip of

the linear actuators

- Connect the impulse lead for the extended thrust rod on connector 2 of the connection

strip terminal.

- Connect the impulse lead for the retracted thrust rod on connector 3 of the connection

strip terminal.

- Replace housing carefully from above and mount with two recessed screws on the linear

actuator.

- Set sliding switch on the housing to automatic operation.
- Connect the supply lines to the mains and move the linear actuator into each of the end

positions in order to test if the end position switches shut off, and if the direction of
movement of the linear actuators is as desired.

- In case the direction of movement is opposite to that which is desired, the impulse cables

for the extending and the retracting thrust rod should be exchanged.

5.4.3.2 ARI-PACO 1,6 Y
- Connect the 24 V AC - voltage supply an connector 1 and V terminals (connector 1 = 0 V)
- Connect the control with a continuous signal of 0(2)...10 V on connector 1 and Y

terminals. (connector 1= 0 V)

- Connect the actuating output signal 0...10 V on connector 1 and A terminals (connector 1=

0 V).

- Connect the actuating output signal 0...10 V on connector 10 and A terminals (for the

normal working direction, connector 10 = 10 V).

- Replace housing carefully from above and mount with two recessed screws on the linear

actuator.

- Connect leads to mains and actuating signal

5.5 Settings

5.5.1 Torque switch off
The torque switch-off is carried out on the linear actuator ARI-PACO 1,6 D and ARI-PACO
1,6 Y
by means of 2 torque switches. (DE1,DE2)

ATTENTION !
- The thrust actuator may only be operated for a short time without the hood for

unavoidable setting operations to the potentiometers, travel switches and the
electrical options. While these operations are in progress, the thrust actuator
has hazardous, live, uninsulated parts exposed as well as moving and rotating
parts.

- Improper execution of the setting operations or lack of care may cause death,

grievous bodily injury or substantial property damage.

- Operation of the thrust actuator without the hood for any purpose other than

that described above is strictly prohibited.