Parameter list, Mvp-svr, Power saver valve controller – High Country Tek MVP-SVR Series User Manual

Page 10

Advertising
background image

021-MVP-SVR Rev A

MVP-SVR User Manual

10

Copyright © High Country Tek, Inc.

– 2013

MVP-SVR

Power Saver Valve Controller

Parameter List

The following table outlines the MVP-SVR parameters as well as the limits and units of measure for each
parameter.

Parameter

Limits

Units

MVP-SVR-xxx

Version #

Start time

0.0 to 6.0

Seconds

Start current

0 to 600

*

mA

Hold current

0 to 600

*

mA

Output current

mA

Supply voltage

Volts

Fault status

Fault

*

0 to 1.2A for

–12A version, 0 to 2.5A for –25A version

MVP-SVR-xxx - The title parameter is fixed. It displays the model number and the firmware version.

START TIME - Sets the amount of time the controller will operate at the Start Current after initial power up. It is

typically very short, allowing only enough time for the valve spool to fully shift.

START CURRENT - Sets the current to the valve during the Start Time after initial power up. This is the max valve

current. The unit is in milliamps (amps for -12A,-25A).

HOLD CURRENT - Sets the current to the valve after the Start Time has expired. It is a percentage of the max

valve current. Always have a margin of error to ensure the valve stays in its on position when activated. The
unit is in milliamps (amps for -12A,-25A).

OUTPUT CURRENT - Displays the present output current. This parameter is a monitor type.

SUPPLY VOLTAGE - Displays the

module’s power supply voltage. It is helpful for troubleshooting. This parameter

is a monitor type.

FAULT STATUS - The STATUS LED will flash red 2 times for Coil Open and 3 times for Coil Short.