Closed-loop Valve Controller

Closed Loop Velocity Mode (DRF2-Vxx)

The DRF can drive a single solenoid valve in closed
loop velocity mode.

Set the input ranges to match the desired command
and feedback range.

NOTE: The feedback (C2 input) setting should be

inverted for reverse-logic valves. The minimum must

be greater than the maximum.

Set the dither and output settings according to the
valve specifications.

Schematic:

FUSE

+V Power Input
9 - 32VDC

+V = Enabled

PWR J1-1

DRF2

Electronic Valve

Controller

Enable J1-3

GND J1-2

-10V Ref. Out J4-1

+10VDC @ 20mA

0 to 10VDC

+10V Ref. Out J4-3

Ch. 1 I/P J5-1

Sig GND J4-2

J5-2

V

D

C

I/

P

m

A

I/

P

Supply Voltage

4-20mA

Ch. 2 I/P J5-3

Prop. PWM (Sourcing)

Sig GND J2-2

Ch. 1 Out J2-1

Ch. 2 Out J2-3

Prop. PWM (Sourcing)

Feedback

Process

Example Settings

Command/Feedback Transfer Diagram

Parameter

Value

C1 Mode

4 VEL USE ENBL

C1 Min input

0.2 V

C1 Max input

10.0 V

C1 Min output

5 mA

C1 Max output

600 mA

C2 Mode

2 IN2 USE ENBL

C2 Min input

0.2 V

C2 Max input

10.0 V

C2 Min output

5 mA

C2 Max output

600 mA

Dither frequency

150 Hz.

Command (C1)

Feedback (C2)

+10V

-10V

0.2V

0.2V

+10V