7. WHS PREMIER SERIES

PIPING INSTALLATION

DOMESTIC WATER PIPING

1. Thread the included brass tee onto the pipe marked COLD

WATER.

2. Screw the drain valve into the opposite end of the brass

tee

3. Connect the cold water supply to the remaining port on the

brass tee

4. Thread the included T&P Safety Relief Valve into the offset

3

/

4

” port on the top plate. Install a blowdown tube to within

6 inches of a floor drain or as directed by plumbing code.

5. Connect the center hot water outlet port on the top plate to

the domestic hot water system.

6. Make an 8-inch “heat trap” as shown in the diagram. This

will reduce standby losses from heat migrating up the

piping.

7. When all domestic water piping is complete, open the cold

water supply and allow some water to enter the tank. Look

and listen for signs of leaks and repair as necessary before

continuing.

Note: If installing on a city supply, ensure a dedicated

Thermal Expansion tank (Therm-X-Trol

®

or equivalent) is

used.

BOILER PIPING

1. Plumb the circulator or zone valve on the BOILER SUPPLY

line. If using a separate circulator, the pump flange

can be mounted directly to the threaded pipe marked

BOILER SUPPLY. Alternately, the circulator can be placed

anywhere on the boiler supply line.

2. Pipe the BOILER RETURN connection to the boiler return

line.

Be sure the return line is NOT

plumbed to the suction side of any

heating circulators. This may require moving the

heating circulator off the boiler tapping on packaged

boilers. Failure to do so will result in overheating and

tank damage when the heating system is in

operation.

3. Install a weighted flow check on the boiler return line. This

is not necessary on systems utilizing a zone valve to control

the BoilerMate

®

temperature.

4. After completing the boiler piping, slowly open the boiler fill

valve and pressurize the BoilerMate

®

loop. Check for leaks

and repair as necessary. Proceed to the appropriate wiring

section in this manual.

If installing on city water supply a

properly sized THERM-X-TROL

®

is

required with the BoilerMate

®

and should be installed as set

forth in the THERM-X-TROL

®

product installation manual.

LEFT SIDE . . . . . . . . . . . . 1”

RIGHT SIDE . . . . . . . . . . . 1”

TOP . . . . . . . . . . . . . . . . . 9”

REAR . . . . . . . . . . . . . . . . 1”

FLOOR . . . . . . . . . . . . . . . 0”

FRONT . . . . . . . . . . . . . . . 1”

Clearance From Combustible Surfaces

LEFT . . . . . . . . . . . . . . . . . 12”

RIGHT. . . . . . . . . . . . . . . . 12”

FRONT . . . . . . . . . . . . . . . 30”

HEAD ROOM . . . . . . . . . . 36”

REAR . . . . . . . . . . . . . . . . 1”

Recommended Clearance For Servicing

HOT WATER OUTLET

BOILER RETURN (Top Left)

BOILER SUPPLY (Top Right)

T&P RELIEF VALVE

COLD WATER INLET

(Bottom Center)