3. REQUIRED COMPONENTS AND

ACCESSORIES CHECKLIST

SHUTOFF

VACUUM

RELIEF THERMAL EXPANSION

MODEL

CIRCULATOR

ZONE VALVE*

VALVE

BREAKER

VALVE

TANK

DRAIN

Residential = 5GPM

*If Circulator not used

Required

WH SERIES Commercial = 10GPM

3/4” Full Port

4

1

Included

(See Therm-X-Trol

®

Included

Except “P” Models

or 1” STD

Sizing Guide)

5GPM

*If Circulator not used

Required

TD SERIES

Except “P” Models

3/4” Full Port

4

1

Included

(See Therm-X-Trol

®

Included

or 1” STD

Sizing Guide)

Required

RTR SERIES

Included

N/A

4

1

Included

(See Therm-X-Trol

®

Included

Sizing Guide)

Residential = 5GPM

*If Circulator not used

Required

WHS SERIES Commercial = 10GPM

3/4” Full Port

4

1

Included

(See Therm-X-Trol

®

Included

Except “P” Models

or 1” STD

Sizing Guide)

ALL INSTALLATIONS REQUIRE TEFLON

®

SEALING TAPE OR PIPE DOPE FOR THREADED JOINTS.

SEE HEAT EXCHANGER PRESSURE DROP CHART TO DETERMINE PUMP HEAD REQUIREMENTS.

Use this chart to select the proper circulator for your BOILERMATE

®

.

If a steel hydropneumatic tank is in place, AMTROL

®

recommends replacing it with a

properly sized EXTROL

®

or Radiant EXTROL

®

expansion tank. Otherwise, significant

heat transfer problems can occur by causing air to be trapped in the heat exchanger. If the boiler system has

an EXTROL

®

or Radiant EXTROL

®

expansion tank and the boiler temperatures are being changed, resize the

EXTROL

®

or Radiant EXTROL

®

expansion tank.