Index – American Water Heater GAS-FIRED COMMERCIAL WATER HEATER User Manual

Page 10

Advertising
background image

10

Figure 2

Non-Flue Damper Models

Model Designation

Clearances *

Capacity

Input

A

B

C

D

Sides and Flue or Ceiling

(GAL) (BTU/hr) (in.) (in.) (in.) (in.) Rear

(in.)

Vent

(in.)

(in.)

65 370,000

71.38

64.38

54.13

8 6 6 20

65 399,999

(NAT ONLY)

71.38

64.38

54.13

8 6 6 20

75 300,000

72.00

64.38

54.13

7 6 7 20

80 425,000

81.00

75.38

64.25

10 6 6 20

80 505,000

81.00

75.38

64.25

10 6 6 20


Model Designation

Clearances *

Capacity

Input

A

B

C

D

Sides and Flue or Ceiling

(Litres) (kW/hr) (m) (m) (m) (cm) Rear

(cm)

Vent

(cm)

(cm)

246.1 108.5 1.82

1.64

1.38 20.4 15.3 15.3 50.8

246.1 117.3

(NAT ONLY)

1.82 1.64 1.38

20.4 15.3 15.3 50.8

283.9 88.0 1.83

1.64

1.38 17.8 15.3 17.8 50.8

302.8 124.6 2.06

1.92

1.64 25.4 15.3 15.3 50.8

302.8 148.0 2.06

1.92

1.64 25.4 15.3 15.3 50.8



Installation (Minimum Clearances) continued-