Part 1 Installation

Specifications

1

___________________________

CAUTION: MPG-Series are not intended for outdoor installation and must be protected

from excessive moisture. Provide adequate clearance for service and proper operation.

Open basements will generally allow sufficient air infiltration, so special provisions will seldom

be required. If the heating plant is located in a separate furnace room or in an unusually tight
basement, permanent means must be provided to supply an ample volume of fresh air for
combustion and boiler room ventilation. A direct opening to the outside air should be provided
sized on the basis of 1/2 square foot of free opening for each 1,000,000 BTU of burner rating
when the vent connector is equipped with a barometric draft control, 11/2 square feet when
equipped with a draft hood. If the ventilation opening is screened, it should be of 11/4" mesh.

Part 1

Installation

2

I

Ventilation

The Midco power gas burner, MPG Series, is designed for firing natural gas or propane
gas in most applications. The burner is a self-contained unit including a blower housing
assembly, a burner gas manifold assembly, a burner cartridge, a flame safeguard, and a
main and pilot gas train. The burner is easy to install, it includes mounting the burner to the
gas utilization equipment, piping the main and pilot gas train and connecting the power
supply. Before shipment every burner is operationally fire tested at the factory, for
unassembled valve trains the pilot solenoid and ignition system is tested.

Burner Style

Power Type Sensing

Pilot Type

Intermittent;

Flame Rod Sensing, Spark Ignition(Standard)

Intermittent;

UV Sensing, Spark Ignition (Optional)

Interrupted;

Flame Rod Sensing, UV Flame Scanner (Optional)

Pilot Safety

Instantaneous Electronic Flame Safeguard

Voltage

Standard

Controls

120/1/60

Motor

115/1/60

230/1/60

(Optional)

U.L. Listed -U.L.C. Listed

Non UL 220V / 50HZ - Contact Factory

MPG 1.5G **

MPG 2.5G **

1500

2500

325

540

4" W.C.

4

4" W.C.

4" W.C.

4

4" W.C.

Natural

Propane

Maximum

Input

1

MBH/HR.*

Maximum

Air

SCFM

3

Models

Inlet Gas Pressure

Required

2

MPG 1.5G

MPG 2.5G

1

/

2

3

/

4

0.13 - 1.20" W.C.

0.09 - 0.80" W.C.

0.08 - 0.70" W.C.

0.06 - 0.50" W.C.

Natural

Propane

Motor HP

(3450 RPM)

See Table 3

See Table 3

Recommended

Combustion

Chamber

Size

Models

Burner Manifold Pressure

1

*1 MBH=1,000 BTU/HR
** High Turn Down Models available - contact factory

1.

Values given based on 0" W.C. firebox pressure, altitudes to 2,000 feet. Derate burner
for altitudes over 2,000 feet by 4% for each 1,000 feet over sea level.

2.

Maximum inlet pressure both gases: 14" W.C. Refer to Section VI Piping for high pressure.

3.

SCFM=Standard Cubic Feet/Minute

4.

Requires special valve train - contact factory

Table 1: Burner Specifications

*1 MBH=1,000 BTU/HR.

See Table 6 for gas pressure and air shutter settings

Models

MPG 1.5G

MPG 2.5G

500

850

1500

2500

1500

2500

1400

2450

1.0

1.0

1200

2000

Maximum Capacity in MBH at

Combustion Chamber-

Back Pressure

0" W.C.

.25" W.C.

.50" W.C.

Minimum

Firing

Rate

MBH*

Maximum

Back

Pressure
in " W.C.

Maximum

MBH* at

Maximum

Back Pressure

Table 2: Maximum Capacity at Specified Back Pressures

500

850

Minimum

Input

1

MBH/HR.*