CAUTION: Do not exceed maximum rated capacity of burner model-See Tables 1 & 2.

Before gas is introduced to the system, a check must be made to see that there are no open

fittings and to make sure the burner main and pilot manual valves are closed. After checking
above, purge the gas line up to the burner inlet. Purging the air from the gas supply line at this
step will expedite the first light-off.

CAUTION: Purge outside the building. Do not purge into the gas utilization equipment

combustion chamber.

___________________________

Burners are approved for use with NATURAL gas or PROPANE gas and should be used only
with the gas specified on the rating plate.

The gas input should be set at the heating rate determined by the building heat loss and/or

heating plant survey, but not exceeding the rated maximum input of the gas utilization equipment.

8

Part 1 Installation

VII

Main Gas

Input Selection

VI

Piping

Continued

20

730

1150

1100

1730

2100

2500

2500

2500

2500

2500

60

400

630

610

960

1150

1800

1850

2500

2500

2500

100

300

480

460

725

870

1370

1400

2200

2500

2500

40

500

785

760

1200

1450

2280

2300

2500

2500

2500

Pipe
Size

1 1/4

1 1/4

1 1/2

1 1/2

2

2

2 1/2

2 1/2

3

3

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

200

330

320

500

610

960

980

1550

1700

2500

Approximate Capacity -MBH

Pipe Length

Type

of Gas

Capacities shown are for a
total pressure drop of
0.3"W.C. For 0.5"W.C.
pressure drop, multiply
capacity shown by 1.3 .
Propane capacities shown
are for a total pressure drop
of 0.5” W.C. For higher
permissible pressure drops,
consult your gas supplier.
Source: Gas Engineers
Handbook - 1974

Table 5: Schedule 40

PT Pipe-Capacity Chart

MPG 1.5 (On-Off) Gas Flow & Air Shutter Setting

Firing Rate

(MBH/Hr)

* 500

700

800

900

1000 1100 1200 1300 1400 1500

Natural gas
manifold pressure

0.13

0.26

0.34

0.43

0.53

0.65

0.77

0.90

1.05

1.20

" W.C. **
Propane gas
manifold pressure

0.08

0.15

0.20

0.25

0.31

0.38

0.45

0.53

0.61

0.70

" W.C. **
Air shutter

position 0.0

0.0

0.2

0.3

0.5

0.8

1.4

2.3

4.0

6.8

MPG 2.5 (On-Off) Gas Flow & Air Shutter Setting

Firing Rate

(MBH/Hr)

* 850

1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500

Natural gas
manifold pressure

0.09

0.29

0.33

0.37

0.41

0.46

0.51

0.56

0.62

0.68

0.74

0.80

" W.C. **
Propane gas
manifold pressure

0.06

0.18

0.20

0.23

0.26

0.29

0.32

0.35

0.39

0.42

0.46

.050

" W.C. **
Air shutter
position 0.0

0.7

0.9

1.1

1.3

1.6

1.8

2.0

2.2

2.5

2.9

3.5

*

1 MBH=1,000 BTU/HR

**

Based on zero chamber pressure at sea level (Chamber pressure can be measured at pilot gas pressure tap with pilot gas off

Table 6: Manifold Gas Pressure and Air Shutter Settings