fire input rate or the recommended minimum input as shown in Table 1, whichever is higher. If
further adjustments are required, screw in or back off the low fire adjustment screw
and adjust the air shutter until a satisfactory flame is achieved. Check combustion per paragraph
13, page 9, and mark the position of the low fire shutter setting with a pencil or scratch mark on
the blower housing.

3 .

With burner switch off, remove jumper from modulating motor terminals "R-W" and reconnect
controller wires to terminals "B" and "W". Reconnect the air shutter connecting rod. Operating
linkage manually, adjust to index marker air shutter positions with high and low positions of the
input adjuster.

4 .

Restart the burner and cycle it several times using the modulating control and the on-off control to
assure proper operation and correct linkage of the air shutter connecting rod. Conclude start-up
procedure per paragraph 15.

After the initial start-up procedure, the following steps can be followed for routine start-up and shut-
down on a seasonal or extended basis.

This table is provided as a guide to use the INPUT ADJUSTING METHOD to approximate final settings.

The valve train M U S T be tested for tightness and the pilot adjusted for proper operation before

proceeding. Refer to Section VIII Burner Box and Firing Head of the this manual.

1 . Install a Manometer (not a

pressure gauge) in the manifold

pressure tap.

2 . Close the Main Manual Gas

V a l v e .

3 . Close the Input Adjuster

(butterfly valve).

4 . Turn the burner on.

5 . Adjust the air shutter to the "Air

Only" pressure shown for the

desired MBH.

6 . Open the Main Manaual Gas

V a l v e .

7 . Slowly open the Input Adjuster

until the observed manifold

pressure equals the Gas On

pressure for the desired MBH.

8 . Take combustion readings and

confirm the input rate by

clocking the gas meter.

9 . Adjust the air shutter and/or the

Input Adjuster as needed.

1 0 . Repeat steps 8 and 9 until you

have the desired input rate with

clean combustion**.

1 1 . Refer to section VIII Burner Box

and Firing Head of this manual

for final Main Gas Regulator

adjustment procedures.

For capacities not shown:

P

2

= P

1

x

(

M B H

2

M B H

1

)

2

*1 MBH=1000 BTU/HR.

ALL FIGURES ARE APPROXIMATE.

Actual figures will vary depending

upon application and ambient

conditions. Based on 0 pressure over

the fire at Standard Air and S p e c i f i c

G r a v i t i e s of .64 for NATURAL GAS,

and 1.52 for PROPANE GAS. It is the

responsibility of the installer to make

final adjustments to insure proper and

safe operating conditions, and to

comply with all codes and guidelines

that may apply at the installation site.

Contact the local Utility for any

requirements and recommendations

they may have. In the absence of any

local codes, guidelines or requirements,

refer to the National Fuel Gas Code,

Model

Capacity

MBH*

Air

Only

Natural

Propane

Manifold Pressures ("W.C.)

Gas On

G56

G57

G58

G69

1075
1000

900
800
700
600
500
300

1500
1300
1200
1000

900
700
600
300

1850
1700
1600
1500
1200
1000

800
500

2500
2200
2000
1800
1500
1200
1000

800

1.00
0.87
0.70
0.55
0.42
0.31
0.22
0.08
1.90
1.43
1.22
0.84
0.68
0.41
0.30
0.08
2.65
2.24
1.98
1.74
1.11
0.77
0.50
0.19
2.25
1.74
1.44
1.17
0.81
0.52
0.36
0.23

2.10
1.82
1.47
1.16
0.89
0.65
0.45
0.16
4.10
3.08
2.62
1.82
1.48
0.89
0.66
0.16
4.60
3.88
3.44
3.02
1.94
1.34
0.86
0.34
4.15
3.21
2.66
2.15
1.49
0.96
0.66
0.42

1.45
1.25
1.01
0.80
0.61
0.45
0.31
0.11
2.79
2.10
1.79
1.24
1.01
0.61
0.45
0.11
3.75
3.17
2.80
2.47
1.58
1.10
0.70
0.27
3.65
2.83
2.34
1.89
1.31
0.84
0.58
0.37

Table 4: Approximate G-Series Capacities at

Specified Manifold Pressures

Burner Start Up
1 .

Make sure line switch is off

2 .

Set controller to call for heat

3 .

Open firing door

4 .

Open Main and Pilot Manual Valves

5 .

Reset flame safeguard

6 .

Turn on line switch

7 .

Close firing door after main flame ignites

8 .

Reset control to desired setting

Burner Shut down
1 .

Turn off main line switch

2 .

Close Main Manual Valve

3 .

Close pilot manual