PAGE 4

15 JAN 2010

MAN0432-04















Figure 5 – Network Connector Figure 6 – As viewed at the RCS






b.

Grounding













Figure 7 – Grounding Method



2.3.3

RS-232 Programming Port and Wiring

Table 4– RS-232 Port Pins

Pin

Signal

Description

Direction

1

DCD

Always high

Out

2

RXD

Received Data

Out

3

TXD

Transmitted Data

In

4

DTR

Data Terminal Ready

In

5

GND

Ground

-

6

DSR

Data Set Ready

Out

7

RTS

Request to Send

In

8

CTS

Clear to Send

Out

9

RI

Ring Indicate

Out

V+

CN_H

SHLD

CN_L

V-

1 2 3 4 5

V-

CN_L

SHLD

CN_H

V+

1 2 3 4 5

Warning: To provide maximum noise immunity and to ensure minimum EMI radiation, the V-
signal (DC power return) need to be connected to earth ground at the power supply. The user must
ensure that the power supply selected is compatible with this method of grounding.

DC Power

Supply

+ -

RCS

+ -

Frame
(Earth)
Ground

Connect DC V- to earth ground at the power supply.