View OCS (RCS) Status


This screen contains both a single enumerated editable field that sets the MiniOCS / MiniRCS scan mode
and status fields that display information about the internal state of the MiniOCS/ MiniRCS. Pressing the

and

keys scrolls through the different items. Pressing Esc returns to the System Menu.


Parameter

Description


OCS Mode

Displays the current scanning mode (Idle, Run, DoIO). In Idle mode, the I/O is
not scanned and the OCS ladder program does not execute. The green “RUN”
LED is OFF. In Run mode, the ladder program executes and the green “RUN”
LED illuminates. DoIO mode is similar to Run mode, except the ladder logic is
not solved. When the OCS is in DoIO mode, the user is able to exercise all of
the I/O from Cscape, without interference from the ladder program. In this mode
the green “RUN” LED flashes. This feature is a valuable troubleshooting tool.


Scan-Rate

Shows the number of milliseconds for the scan. The scan-rate is the sum of the
time required to execute the following items:

a. Scan inputs
b. Solve logic
c. Write outputs
d. Handle network communications
e. Handle host communications request
f.

Process data for operator interface


OCS Net Use

Shows the percentage of the network used by the Mini.

All Net Use

Shows the percentage of the network used by all devices on the network.



Ladder Size

Shows the number of bytes used by the ladder program.

Config Size

Shows the number of bytes used by the I/O configuration


Text Size

Shows the number of bytes used by the text screens

Firmware Rev

Shows the execution engine firmware version.

BIOS Rev

Shows the BIOS firmware revision.

FPGA Rev

Shows the FPGA Image version.

Self-Test

Shows if the power-up self-test passed or failed by displaying Ok or Fault.