BASIC SMARTSTIX PROGRAMMING

6.4

Using GET and PUT


6.4.1

Get Remote I/O Function Block


This function handles receiving data from a remote I/O device and places the received data in a set of
registers specified by the user. This function passes power flow if the function is actively receiving data /
heartbeat messages from the remote I/O device. This function stops passing power flow if it has not
received data / heartbeat messages from the remote I/O device for 2000 milliseconds.

A remote I/O device consists of a CsCAN device such as a SmartStix Module that transmits global data
and receives directed network data.




















Figure 6.1 – Get Remote I/O Function Block and Parameter Screen



6.4.2

Get Remote Parameter Description:


ID – This is the network ID of the remote I/O from which to receive data. This can be a constant from 1 to
253 or a 16-bit register.

Digital / Analog – These radio buttons allow choosing digital or analog network data. Remote I/O
devices with discrete inputs/outputs normally require digital data. Remote I/O devices such as voltage,
current or thermocouple would require analog data.

Destination Data Address – This is the location to start placing data received from the remote I/O
device. The number of registers used is defined by the Num Words parameter in this section. Any valid
read/write OCS reference types can be used (%R, %AI, %I, %M, etc.).

Status – This 16-bit register is used internally. It must not written by any other function block. Use the
power flow from this function for the pass/fail status.