5. NETWORK DATA

Consumed Digital Data

– This data is sent from the controller to the SmartBlock. For typical applications, the I/O configuration setup in

Cscape will automatically populate this data. For more advanced applications, you may use NetPut functions to write this data. Please
see the advanced programming guide MAN0880 for more details.

Bit

Description

1-8

Digital Outputs

Bits that control the relay or DC outputs

9-64

Reserved

65-72

Output Hold

1 = Hold on stop, 0 = Override

73-79

Reserved

80

Positive/Negative Inputs

0 = Positive Logic, 1 = Negative Logic

81-96

Reserved

97-104

Output Override Data

Output on stop when hold = 0

105-120

Reserved

Produced Digital Data

– This data is sent from the SmartBlock to the controller. Normally this data is mapped into specific registers in

the I/O configuration in Cscape. For advanced applications, NetGet functions can be used to obtain this data. Since this data is
broadcasted to all controllers on the network, additional controllers can use NetGet functions to obtain this data as well.

Bit

Description

1-8

Digital Inputs

Data from the digital inputs

9

HE579DIQ881

0 = OK, 1 = Fault on output channels 1-4

10

HE579DIQ881

0 = OK, 1 = Fault on output channels 5-8

11-32

Reserved

33-48

Status & Diagnosis Data

49-56

Firmware Version

57-64

Device Class

2

6. SETTING ID SWITCHES

CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The decimal equivalents are whole numbers 1-253.
Refer to following Conversion Table, which shows the decimal equivalent of hexadecimal numbers. Set a unique Network ID by
inserting a small flat-bladed screwdriver into the two identical switches.