3-4. Quick hook – up and testing

For a quick hook – up of the power inverter to check its performance
before going ahead with installation, please follow these guidelines:

3-4-1. To check its performance, unpack and inspect the power inverter the

switch is OFF.

3-4-2. Connect the cables to the power input terminals on the rear panel of

power inverter. The red terminal represents positive (+) and black
terminal represents negative (-). Insert the cables into the terminals
and clamp the nuts and the wires securely.

WARNING!
You may observe a spark when you make this
connection since current may flow into charge
capacitors in the power inverter.
Do not make this connection with the flammable
fumes close by. Explosion or fire may occur.

Ensure all the DC connections are tight (torque to 9 -
10) ft-lbs, 11.7 – 13 Nm. Loose connections and
overheat may result in a potential hazard.

WARNING!

10

Advertising