3 cr1000 program example, Cr1000 program example – Campbell Scientific CURS100 100 Ohm Current Shunt Terminal Input Module User Manual

Page 15

Advertising
background image

CURS100 100 Ohm Current Shunt Terminal Input Module

and at 700 psi is:

V = 0.020

× 100

V = 2.0 V or 2000 mV

Since the datalogger measures in mV, the multiplier (or slope) must be in units
of psi/mV. Therefore, the y values have the units psi and the x values mV.

The equation of a line is:

(y ─ y1) = m (x ─ x1)

Solve the equation for m that is the slope of the line (or multiplier).

m

psi

psi

mV

mV

psi

mV

=

=

700

200

2000

400

0 3125

.

Now replace the known values to determine the intercept (or offset). Where y
= m(x) + b

psi

b

b

mV

mV

psi

psi

75

400

3125

.

0

200

400

3125

.

0

200

=

Ч

=

+

Ч

=

m = multiplier (slope) = 0.3125 and

b = the offset (intercept) = 75.0.

5.3 CR1000 Program Example

'CR1000 program example for sensor with 4-20mA output.

'Assuming a flow meter that outputs a 4-20mA signal representing 0 - 100 gal/min,
'the voltage across the resistor at 0 gal/min = 4mA * 100 ohms = 400mV,
'and at 100 gal/min is 20mA * 100 ohms = 2000mV. The change in mV is
'2000mV - 400mV = 1600mV for 0 - 100 gal/min flow rate.

'The measurement result (X) for the VoltDiff instruction is mV. The
'multiplier to convert mV to gal/min is: mV * 100gal/min / 1600mV = 0.0625,
'the offset is 400mV * .0625 = -25.0.

Public Measure

DataTable (Hourly,True,-1)
DataInterval

(0,60,Min,0)

Average

(1,Measure,IEEE4,0)

EndTable