4 cr9000(x) program example, 5 cr10(x) program example, 6 cr23x program example – Campbell Scientific CURS100 100 Ohm Current Shunt Terminal Input Module User Manual

Page 16: Cr9000(x) program example, Cr10(x) program example, Cr23x program example

Advertising
background image

CURS100 100 Ohm Current Shunt Terminal Input Module

10

BeginProg
Scan (1,Sec,1,0)

'Generic 4-20 mA Input measurement Measure:

VoltDiff

(Measure,1,mV2500,1,True,0,_60Hz,0.0625,-25.0)

CallTable

(Hourly)

NextScan
EndProg

5.4 CR9000(X) Program Example

VoltDiff(Press_psi, 1, mV5000, 5, 1, 1, 0, 0, 0.3125, 75)

5.5 CR10(X) Program Example

1: Volt (Diff) (P2)
1:

1

Reps

2:

25

± 2500 mV 60 Hz Rejection Range

3:

1

DIFF

Channel

4:

1

Loc [ Press_psi ]

5:

0.3125 Mult

6:

75

Offset

5.6 CR23X Program Example

1: Volt (Diff) (P2)
1:

1

Reps

2:

25

± 5000 mV, 60 Hz Reject, Fast Range

3:

1

DIFF

Channel

4:

1

Loc [ Press_psi ]

5:

0.3125 Mult

6:

75

Offset