Campbell Scientific SDM-CD16D 16-Channel Digital Control Port Expansion Module User Manual

Page 16

Advertising
background image

SDM-CD16D 16 Channel Digital Control Port Expansion Module

16: If (X<=>F) (P89)

check lower threshold to

1: 1

-- X Loc [ Temp_1 ]

see if cooler should be

2: 4

<

turned off

3: 24.5

F

4: 30

Then

Do


17: Z=F (P30)

if cooler should be turned off

1: 0

F

put a ‘0’ into cooler control

2: 0

Exponent

of

1

location

3: 15

-- Z Loc [ Cool_1 ]


18: End (P95)

end ‘then do’


19: Else (P94)

else, if cooler is off


20: Z=F (P30)

put a ‘0’ into cooler

1: 0

F

control location

2: 0

Exponent

of

10

3: 15

-- Z Loc [ Cool_1 ]


21: End (P95)

end ‘then do/else’


End cooler control logic

Start fan control logic based on heater/cooler

22: If (X<=>F) (P89)

if heater is on

1: 10

-- X Loc [ Heat_1 ]

2: 2

<>

3: 0

F

4: 11

Set Flag 1 High

set flag 1


23: If (X<=>F) (P89)

if cooler is on

1: 15

-- X Loc [ Cool_1 ]

2: 2

<>

3: 0

F

4: 11

Set Flag 1 High

set flag 1


24: If Flag/Port (P91)

if flag 1 is set

1: 11

Do if Flag 1 is High

2: 30

Then

Do

then


25: Z=F (P30)

put a ‘1’ into fan control

1: 1

F

location

2: 0

Exponent

of

10

3: 20

-- Z Loc [ Fan_1 ]


26: Else (P94)

else, if flag 1 is reset


27: Z=F (P30)

put a ‘0’ into fan control

1: 0

F

location

2: 0

Exponent

of

10

3: 20

-- Z Loc [ Fan_1 ]