SDM-CD16D 16 Channel Digital Control Port Expansion Module

28: End (P95)

end ‘then do/else’


29: Do (P86)

reset flag 1

1: 21

Set Flag 1 Low


30: End (P95)

end master loop


End fan control logic based on heater/cooler

Start fan control logic based on time

31: If time is (P92)

if 5 minutes remain

1: 10

Minutes (Seconds --) into a

out of 15 minute

2: 15

Interval (same units as above)

interval

3: 12

Set Flag 2 High

set flag 2


32: If Flag/Port (P91)

if flag 2 is set

1: 12

Do if Flag 2 is High

2: 30

Then

Do

then


33: Beginning of Loop (P87)

start fan loop

1: 0

Delay

2: 5

Loop

Count


34: Z=F (P30)

put a ‘1’ into fan control

1: 1

F

location

2: 0

Exponent

of

10

3: 20

-- Z Loc [ Fan_1 ]


35: End (P95)

end fan loop


36: End (P95)

end’ then do’


37: If time is (P92)

reset flag 2 at the

1: 0

Minutes (Seconds --) into a

end of the 15 minutes

2: 15

Interval (same units as above)

3: 22

Set Flag 2 Low


End fan control logic based on time

Input locations 10 to 24 are now loaded with a ‘1’ or ‘0’ to set ports on the SDM-CD16D

38: SDM-CD16 / SDM-CD16D (P104)

send instructions to the

1: 1

Reps

SDM-CD16D with address 00

2: 00

Address

3: 10

Loc [ Heat_1 ]


*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)

13