SDM-IO16 16 Channel Input/Output Expansion Module

*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)


*Table 3 Subroutines

End Program

7.3 A CR10X Program which Measures Four Frequency Inputs

(Anemometers) and Four Switch Closure Inputs (Rain
Gauges)

This program can also be used with a CR23X datalogger.

;{CR10X}
;An example that shows initial setup with frequency measurement
;on four ports and pulse counting, with switch closure, on the next
;four. In this example the four frequencies are anemometers and
;the switch closures are raingauges that need to be totalised
;
*Table 1 Program
01: 5

Execution

Interval

(seconds)


;First configure the IO16 if not already done
;If flag 1 is not set, i.e. the program has just
;been compiled or datalogger powered up.
;This code is needed primarily to enable switch debounce filtering
;on channels 4..8

1: If Flag/Port (P91)
1: 21

Do if Flag 1 is Low

2: 30

Then

Do


; Call instruction 188 to set the ports up
2: SDM-IO16 (P188)
1: 0

SDM

Address

2: 90

Command

Code

Option

;configure the ports

3: 9999

Ports

16-13

;Leave the last 8 ports as they are

4: 9999

Ports

12-9

5: 3333

Ports

8-5

;Set ports 5..8 as switch closure

6: 2222

Ports

4-1

;Set ports 1..4 as normal inputs

7: 1

Return Code Loc [ ErrCount ]

8: 2

First Loc [ Windspd_1 ]

9: 1.0

Mult

10: 0.0

Offset


;Set flag 1 high to indicate we have run the setup code
3: Do (P86)
1: 11

Set Flag 1 High


4: End (P95)

; of IF block