Environmental overview – ADIC Scalar 1000 User Manual

Page 19

Advertising
background image

Environmental Overview

The Scalar 1000 library has unique electrical specifi-

cations for the control module, expansion modules, and
tape drives as illustrated in the table below. These de-
scriptions vary from power consumption to special
power supply parameters.

Control Module Electrical Specifications

Each Scalar 1000 module requires a dedicated,

hardwired 20 amp circuit. This must be in place before
Scalar 1000 modules can be installed.

Control Module (Single Phase)

North America

Europe

Voltage

a

115

230

KVA

1.6

1.6

AMP

b

14

7

KW/hour

0.36

0.36

Receptacle

d

L5-20

c

Expansion Module Electrical Specifications

Expansion Module (Single Phase)

North America

Europe

Voltage

a

115

230

KVA

1.6

1.6

AMP

14

7

KW/hour

0.36

0.36

Receptacle

d

L5-20

c

a. Connect an 18-gauge stranded copper wire from the

control module cabinet to an earth ground.

b. Includes the drive components.
c. Cable and receptacle determined by location.
d. To ensure adequate power supply, the Scalar 1000

library requires a dedicated, hardwired 20 amp
circuit and an L5-20 type connector, commonly
referred to as a “20 amp/twist lock” connector.

seventeen

Environmental Overview

Scalar 1000 Drive Component
Electrical Specifications

Device

a

(Single Phase)

DLT 7000

AIT1

3590

(pair of drives)

Voltage

100-240 VAC

100-240 VAC

100-240 VAC

KVA

0.1

0.1

0.25

AMP

1

1

2.5

BTU Guidelines

For customers interested in the BTU (British Ther-

mal Unit) values associated with a Scalar 1000 library,
here are some general guidelines:

DLT

• Control module with 12 DLT drives - 4500 BTU/hr

• 12 DLT drives at steady state - 126 BTU/hr

• 12 DLT drives during operative mode - 160 BTU/hr

AIT

• Control module with 12 AIT drives - 575 BTU/hr

• AIT drive module (drive pair) at steady state - 18 BTU/hr

• AIT drive module (drive pair) during operative mode - 18 BTU/hr

IBM 3590

• IBM 3590 drive module at steady state - 73 BTU/hr

• IBM 3590 drive module during operative mode - 73 BTU/hr

Advertising