Page 6 of 8

CAUSE

SOLUTION

PROBLEM

1. SET POINT DIFFICULT TO SET OR

CANNOT BE REACHED

SUPPLY TEMPS NOT WITHIN
SPECIFIED LIMITS

HOT AND COLD SUPPLIES ARE
REVERSED

CHECK DIFFERENTIAL TEMPERATURE
BETWEEN SUPPLIES AND OUTLET

REINSTALL VALVE WITH SUPPLIES
CONNECTED TO MARKED INLETS

2. DOES NOT MAINTAIN OUTLET

TEMPERATURE OR CHANGES

FLUCUATION IN SUPPLY
PRESSURES

CHECK VALVE/FILTERS BLOCKED
WITH DEBRIS

CHECK DIFFERENTIAL TEMPERATURE
BETWEEN SUPPLIES AND OUTLET

CLEAN CHECK VALVES/FILTERS

OVER TIME

3. DISCHARGE TEMPERATURE TOO

HOT OR TOO COLD

VALVE NOT ADJUSTED PROPERLY

READJUST VALVE TEMPERATURE PER
INSTALLATION INSTRUCTIONS

4. CROSS FLOW

CHECK VALVES FOULED

CLEAN CHECK VALVES/FILTERS

5 NO FLOW FROM VALVE

HOT OR COLD SUPPLY FAILURE
OR SHUTOFFS CLOSED

OPEN SHUTOFFS OR RESTORE HOT
AND COLD SUPPLIES

CHECK VALVE/FILTERS BLOCKED
WITH DEBRIS

CLEAN CHECK VALVES AND FILTERS

*Under Normal Operating Conditions.

Valve Specifications Continues:

Minimum Flow Rate per ASSE 1017*:
MV17-1: ......................................................... 0.5 gpm (1.9 lpm)
MV17-2: ............................................................ 1 gpm (3.8 lpm)
MV17-3: ............................................................ 2 gpm (7.6 lpm)
MV17-4: .......................................................... 3 gpm (11.4 lpm)
MV17-5: .......................................................... 4 gpm (15.1 lpm)

Valve Specifications:

Maximum Operating Pressure: ..................... 125 psi (861 kpa)

Maximum Hot Water Supply Temp: ..................... 180°F (82°C)

Outlet Temp. Range: ............................ 100°-160°F (38°-71°C)

Minimum Hot Water Supply* ....................................... 5°F (3°C)
Above Set Point

Flow Rate at 45 psi (310 kpa) differential:
MV17-1: ........................................................... 12 gpm (45 lpm)
MV17-2: ......................................................... 45 gpm (170 lpm)
MV17-3: ......................................................... 90 gpm (341 lpm)
MV17-4: ....................................................... 150 gpm (568 lpm)
MV17-5: ....................................................... 225 gpm (852 lpm)

TROUBLESHOOTING:

PIPING DETAILS:

Acorn Controls

Division of Acorn Engineering Company

®

, A member of Morris Group International

Date: 04/01/14

NOTE:

ASSE 1017 performance based on actual demand or
recirculation pump flow rate or a combination of both.
See FEATURES regarding control performance at
ZERO GPM user demand.

SFMV Installation & Operation Manual

Manual #7802-118-000

TYPICAL SHOWER PIPING DETAIL

MV17 SERIES

VALVE

TYPICAL SINGLE TEMP LAVATORY PIPING DETAIL

HOT

WATER

SUPPLY

COLD

WATER

SUPPLY

HOT

WATER

SUPPLY

COLD

WATER

SUPPLY

MV17 SERIES

VALVE

LAVATORY
MIXING

VALVES

SHOWER

VALVES

Advertising