Recirculating piping diagram, Acorn controls, Sfmv installation & operation manual – Acorn SFMV VALVE User Manual

Page 7: Division of acorn engineering company, A member of morris group international

Advertising
background image

A C O R N

RECIRCULATING PIPING DIAGRAM:

WATER

HEATER

C

C

T

T

EXPANSION

TANK

HIGH TEMPERATURE

HOT WATER FIXTURES

LOW TEMPERATURE

HOT WATER FIXTURES

HEAT

TRAP

CONTROL

VALVE

BALANCING

VALVE

LOW TEMP
FIXTURE
RETURN

HIGH TEMP

FIXTURE RETURN

T

C

CHECK VALVE

BALANCING VALVE

TEMP/PRESSURE GAUGE

CIRCULATOR

FLOW DIRECTION

C

SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOWRATE.
SEE LITERATURE.

COLD

WATER

SUPPLY

TYPICAL CONTINUOUS RECIRCULATION

WATER

HEATER

C

C

T

T

EXPANSION

TANK

HIGH TEMPERATURE

HOT WATER FIXTURES

LOW TEMPERATURE

HOT WATER FIXTURES

HEAT

TRAP

CONTROL

VALVE

BALANCING

VALVE

LOW TEMP
FIXTURE
RETURN

HIGH TEMP

FIXTURE RETURN

T

C

CHECK VALVE

BALANCING VALVE

TEMP/PRESSURE GAUGE

CIRCULATOR

FLOW DIRECTION

C

SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOWRATE.
SEE LITERATURE.

COLD

WATER

SUPPLY

TYPICAL RECIRCULATION WITH AQUASTAT

ADJUSTABLE
AQUASTAT

NOTE: TO BALANCE THE SYSTEM BEGIN WITH DIVERTING 80% OF THE
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE
WATER HEATER.

NOTE: TO BALANCE THE SYSTEM BEGIN WITH DIVERTING 80% OF THE
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE
WATER HEATER.

Page 7 of 8

Acorn Controls

Division of Acorn Engineering Company

®

, A member of Morris Group International

SFMV Installation & Operation Manual

Date: 04/01/14

Manual #7802-118-000