A.J. Antunes & Co SMD 8021202103 User Manual

Smd installation information, Smd switches, Dimensions

Advertising
background image

1-630-784-1000 Fax: 630-784-1651

Page 1 of 4

P/N 1011083 06/10

1-800-253-2991

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188

SMD Switches

You are installing one of the finest switches of its type on

the market. You will find this switch has many superior

features that ensure dependable, accurate, long life oper-

ation. This switch is highly sensitive and fully approved. It

is UL and CSA listed and has FM approval (optional).

Dimensions

IMPORTANT

Please read these instructions carefully to assure

correct installation. This equipment must be

installed only by a licensed electrician who is

experienced with combustion safeguard control

systems and understands the functions of inter-

locking switches, such as gas pressure switches.

Prior to being put into operation in conjunction

with the combustion safeguard systems, all

switches should be tested for proper range setting

and proper wiring. Check piping connections and

switch house for leaks with a soap bubble test. All

exhaust fans and blowers should be inspected and

checked for proper rotation prior to starting up.

SMD Installation Information

Specifications

Electrical Ratings: 10A @ 125 VAC, 8A @ 250 VAC, 7A

@ 277 VAC, 1/8 HP @125 VAC, 1/4 HP @ 250 VAC

Pilot Duty, 125 VA @ 125/277 VAC
Max. Surge Pressure: 20” W.C.
Max. Ambient Operating Temperature: 170°F (77°C)
Min. Ambient Operating Temperature: -40°F (-40°C)
Shipping Weight: 1 lbs. (.45 kg)
Optional Fittings:
1/4” Barb
1/4” Tube
1/4” Compression

Range Adjustment

All settings are made with the diaphragm in a vertical

position. The switch is shipped with the adjustment at

minimum .17” W. C.

To adjust, turn adjusting screw with screwdriver. To

increase pressure setting, turn adjustment screw in a

clockwise direction. To decrease pressure setting, turn

adjusting screw in a counterclockwise direction.

If adjusting screw is removed, apply a non-hardening

pipe compound to the threads before replacing. Check for

leaks with a soap bubble test using maximum 20” W.C.

Installation

Models may be mounted in the horizontal or vertical posi-

tion. All switches are tested at the factory in a vertical

position. Mounting diaphragm in vertical position is the

preferred method.

If mounting in horizontal position, the micro switch must

be on top. When mounted in this position, the minimum

sensitivity may be higher than that specified.

2 1/4”

(57 mm)

4 13/32”

(112 mm)

3 19/32”

(91 mm)

Mounting holes

for #8 screw

Standpipe with

adjusting screw

1/2” Conduit

Knockout

3”

(76 mm)

NOTE: Dimensions are

for reference only.

Switch Differential

Switch Differential @ 70º F

Differential

Operating Pressure

Range

.015” to .03” W.C.

.17”–1” W.C.

.5” W.C.

.17”–6” W.C.

1.0” W.C.

.17”–12” W.C.