CAUTION

Perform the wiring with sufficient capacity. Installation legally requires a
short circuit isolator to be attached to prevent electrical shock.


Do not extend the power cable cord by cutting.

Power voltage should be in the range of 90% ~110% of rated voltage.

The plug of the air conditioner takes a grounding leg, so clients should
use a grounding socket so that the air conditioner can be
grounded efficiently.

EvAPORATOR INSTALLATION (INDOOR)

4) Wiring

Prepare the power source for exclusive use with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner.

Model

Power Source

Plug socket and

fuse rating

AWG (MIN)

Power Supply Cord

Connecting Cable

<12000Btu/h

60 Hz 115V~

32/25A

14

18

>12000Btu/h

5) Connecting Cables

i) Evaporator (Indoor) and Condensor (Outdoor) connecting cable should be Aw18 or more.
ii) Remove the panel and screw, then remove the window cover (for <12000Btu/h models).

Remove the panel screws covers , then remove the screws and take out the frame

(for model >12000Btu/h models)
iii) Connect cables according to their marks to terminals.
iv) Wrap those cables not connected with terminals with insula-

tion tapes, so that they will not touch any electrical components.

Frame

Panel

Window Cover

Screw

Screw Cover

Panel

Frame

To outdoor

unit

Terminal block of indoor unit

Code Wire

0.4”

1.6”

< 12000Btu/h models

> 12000Btu/h models

10

Advertising