Pressure adjustment – Amtrol WELL-X1 User Manual

Page 11

Advertising
background image

11

1. To enter the programming mode, press and hold the

MODE button until LO appears. This is the cut-in
setting. Factory default will be 40 psi.

2. Use the

s

and

t

arrows to raise or lower the cut-

in setting. Adjustment can be made within 10 psig or
as wide as 55 psig of the cut-out setting to 60 psig. If
this range is exceeded, the display will cease to change
even though the button is being pressed.

Minimum setting is 10 psig.

PRESSURE ADJUSTMENT

The Well-X1

utilizes a simple cut-in/cut-out adjustment. Before setting the desired operating range, refer to the chart

below to ensure the Well-X1's Maximum Acceptance is not exceeded. Adjust the precharge as shown on page 12.

CAUTION! Exceeding Maximum Acceptance will reduce tank life and cause irreparable damage.

CUT-OUT PRESSURE

CUT

-IN PRESSURE

20 25 30 35 40 45 50 55 60 65 70 75

80

10 .28 .38 .45 .50 .55 .59 .62 .65 .67 .69
15

.25 .34 .40 .46 .50 .54 .57 .60 .63 .65

20

.22 .30 .37 .42 .46 .50 .64 .57 .59 .61

25

.20 .27 .34 .39 .43 .47 .50 .53 .56 .58

30

.18 .25 .31 .36 .40 .44 .47 .50 .53

35

.17 .23 .29 .34 .38 .41 .45 .48

40

.16 .22 .27 .31 .35 .39 .42

45

.14 .20 .25 .30 .33 .37

50

.13 .19 .24 .28 .32

55

.13 .18 .22 .26

60

.12 .17 .21

65

.12 .16

70

.11

Step 1: Find the Maximum Acceptance for the installed
Well-X1

model.

Step 2: Ensure the desired operating range does not
exceed that model's Maximum Acceptance.

MODEL

MAXIMUM

ACCEPTANCE

WX1-202

.57

WX1-203

.35

WX1-250

.77

WX1-251

.55

WX1-302

.54

PRESS AND

HOLD TO

UNLOCK AND

SET CUT-IN

t

t