Aprilaire 1150 User Manual

Page 25

Advertising
background image

Notes:

• Dashed lines indicate provided by installer.

• The water supply inlet is more than 1” (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the chamber.

No additional backflow prevention is required; however, governing codes prevail.

Shock arrester

recommended to

reduce water hammer

Water supply line

Spill funnel;

plumb to

floor drain

1” (25 mm)

air gap

¾” (DN20) copper

chamber drain

and overflow

piping, rated for

140°F (60°C).

If piping run

is over 10’ (3 m)

increase pipe to

1¼” (DN32).

Open drain required. Locate air gap only in

spaces with adequate temperature and air

movement to absorb flash steam; otherwise,

condensing on nearby surfaces may occur.

Refer to governing codes for drain pipe size

and maximum discharge water temperature.

Install plumb

Steam hose

(maximum run 10’ [3 m])

OM-4010

Union by installer

¼” (DN8) compression

fitting on fill valve

connection to water

supply line; water

pressure must be between

25 psi and 80 psi

(175 kPa and 550 kPa);

water conductivity

minimum 100 µS/cm

2

;

fill valve has an integral

strainer

FIGURE 22 – Field Piping Overview Showing Hard Pipe Drain Connections

25

Advertising
This manual is related to the following products: