DISTRIBUTION DRIP TEE INSTALLATION

If the humidifier cannot be mounted below the steam distribution tube, such that there is a minimum 2”/ft (15%) pitch along the
entire hose length, a drip tee as shown below must be installed. Failure to follow the recommendations on this page, when the
humidifier is mounted higher than the distribution tube, can result in excessive back pressures on the humidifier. This may lead to
distribution tube spitting, steam blowing through the P-trap before the plumbing system, or leaking gasket.

IMPORTANT: Steam hose must be supported to prevent sagging or low spots.

OM-4009

������

�����

����

�����

Humidifier

Funnel or floor drain.

Refer to governing codes for

drain pipe size and maximum

temperature requirements.

1” (25 mm)

air gap

8” (200 mm)

minimum

6” (150 mm) recommended

To distribution

tube

Dashed lines indicate

provided by installer.

¾” (DN20)

Steam hose

or hard pipe

Insulate tubing and

hard pipe to reduce

steam loss

Copper tubing or pipe drip tee,

by installer

FIGURE 23 – Drip Tee Installation