Panasonic KE18NB4U User Manual

Page 44

Advertising
background image

For the removal of the following components, perform any work after removing the indoor

unit (main body) from the ceiling.

Main body lower section

Heat exchanger sensor

Drain pump

Float switch

Turbo fan

Fan motor

Heat exchanger

1. Perform the work after draining the water to prevent the water leakage from the drain pan.

Put a bucket, etc., under the drain cap and remove the drain cap to drain the water.

(Fig. 16)

2. Refer to the installation instructions for recovery of refrigerant or removal of the power

cable or tubing.

7-3-6. Remove the main body lower section.

(1) Remove the 4 screws. (Fig. 16)

(2) Remove the 2 screws. (Fig. 17)

(3) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18)

(4) Lift the main body lower section and remove it from the main body upper section.

Screw

Fig.16

Fig.18

Fig.17

Drain cap

Main body lower section

Main body lower section

Screw

Screw

Main body lower section

Main body
upper section

Screw

CN03

Screw

NOTE

44

Advertising
This manual is related to the following products: