Istema, De refrigeración, Aintenance – Nor-Lake Capsule Pak Refrigeration Systems User Manual

Page 22: Nalysis, Malfunction possible cause solution

Advertising
background image

22

07/14 Rev. H 040086

m

aintenanCe

a

nalySiS

malfunCtion

poSSible CauSe

Solution

Compressor will not start -

1. Unplugged or power off

1. Plug in service cord or turn power on

no hum

2. Fuse blown or removed

2. Replace fuse

3. Overload tripped

3. Determine reasons and correct

4. Control stuck open

4. Repair or replace

5. Wiring incorrect

5. Check wiring against the diagram

Compressor will not start -

1. Improperly wired

1. Check wiring against the diagram

hums but trips on overload

2. Low voltage to unit

2. Determine reason and correct

protector

3. Starting capacitor defective

3. Determine reason and replace

4. Relay failing to close

4. Determine reason, correct or replace

Compressor starts and runs,

1. Low voltage to unit

1. Determine reason and correct

but short cycles on overload

2. Overload defective

2. Check current, replace overload protector

protector

3. Excessive head pressure

3. Check ventilation or restriction in

refrigeration system

4. Compressor hot — warm ambient

4. Check refrigerant charge, fix leak if

conditions

necessary

Compressor operates long

1. Short of refrigerant

1. Fix leak, add charge

or continuously

2. Control contact stuck

2. Repair or replace

3. Evaporator coil iced

3. Determine cause, defrost manually

4. Restriction in refrigeration system

4. Determine location and remove restriction

5. Dirty condenser —warm ambient

5. Clean condenser

conditions

Compressor runs fine, but

1. Overload protector

1. Check wiring diagram

short cycles

2. Cold control

2. Differential too close - widen

3. Overcharge

3. Reduce charge

4. Air in system

4. Purge and recharge

5. Undercharge

5. Fix leak, add refrigerant

Starting capacitor open,

1. Relay contacts stuck

1. Clean contacts or replace relay

shorted or blown

2. Low voltage to unit

2. Determine reason and correct

3. Improper relay

3. Replace

Relay defective or burned out

1. Incorrect relay

1. Check and replace

2. Voltage too high or too low

2. Determine reason and correct

Refrigerated space too warm

1. Control setting too high

1. Reset control

2. Refrigerant overcharge

2. Purge refrigerant

3. Dirty condenser

3. Clean condenser

4. Evaporator coil iced

4. Determine reason and defrost

5. Not operating

5. Determine reason, replace if necessary

6. Air flow to condenser or

6. Remove obstruction for free air flow — no storage

evaporator blocked

on top of walk-in

7. Warm ambient conditions

7. Ambient conditions should be 90° or less

Standard temperature system

1. Control setting is too low

1. Reset the control

freezes the product

2. Control points stuck

2. Replace the control

Objectionable noise

1. Fan blade hitting fan shroud

1. Reform or cut away small section of shroud

2. Tubing rattle

2. Locate and reform

3. Vibrating fan blade

3. Replace fan blade

4. Condenser fan motor rattles

4. Check motor bracket mounting, tighten

5. General vibration

5. Compressor suspension bolts not loosened

on applicable models - loosen them

6. Worn fan motor bearings

6. Replace fan motor

Water overflowing from

1. Air leak between refrigeration system

1. Check that refrigeration system is properly set

evaporator drain pan or

and walk-in panel.

in panel opening.

condensate vaporizer pan

2. Drain line from evaporator drain

2. Clean blockage from inside of drain line.

pan to condensate vaporizer is

blocked with foreign material.

3. Drain line from evaporator drain

3. Check that drain line heater (on freezers)

pan to condensate vaporizer is

is working and repair or replace as required.

blocked with ice.

4. Walk-in operating in high humidity

4. Plumb drain line from evaporator to floor

environment (heavy door usage).

drain or replace high gas vaporizer with

electric vaporizer. Consult factory for

further

information.