D. post-installation and start-up checklist – Amtrol TD-7ZDW User Manual

Page 9

Advertising
background image

-9-

the service switch).

c. Switch off the branch circuit breaker.

Step 2 - Remove electrical box cover.

Step 3 - Remove existing wire from boiler aquastat

terminal C1 and connect to terminal #2 on
DPDT relay.

Step 4 - Install wire from DPDT relay terminal #1 to boiler

aquastat terminal C1.

Step 5 - Connect terminals of 4 and 6 of DPDT relay "T-

T" terminals of boiler aquastat relay.

Step 6 - Connect BOILER MATE™ thermostat to L1,

BOILER MATE™ and DPDT relay as shown
in Schematic #4.

Step 7 - Connect L2 to BOILER MATE™ circulator

and DPDT relay as shown in Schematic #4.

B. Use only the heating system circulator.

When wiring a separate, full-flow 3-way zone valve, follow
steps in 1B. above.

Note: Priority comes from the valve operation and not the
wiring.

D. POST-INSTALLATION and
START-UP CHECKLIST

After the BOILER MATE™ has been plumbed and wired, it is now
ready to be set for automatic operation. Turn on the boiler and
safety switches.

TEMPERATURE ADJUSTMENT

PAINFUL SCALDING WITH POSSIBLE
SERIOUS AND PERMANENT INJURY

CAN OCCUR IF THE TEMPERATURE IS SET TOO HIGH OR
THE THERMOSTAT IS NOT FUNCTIONING PROPERLY.

The thermostat controls the maximum water temperature in the
BOILER MATE™. If set too high, the resulting hot water can
cause painful scalding with possible serious and permanent
injury.

The temperature at which this occurs varies with a

person’s age and the length of time in contact with the water.
The slower response time of infants, aged or handicapped
persons increases the hazard to them.

It is recommended that the temperature control be set for the

lowest temperature which satisfies your hot water needs. This will
also provide the lowest operating costs.

In conjunction with a Consumer Product Safety Commission
recommendation, an initial setting of 120° F is recommended.
This may or may not be suitable for your needs. Check the
temperature at a hot water faucet soon after the burner has
completed the first heating. Adjust as needed. Note that
adjusting to a lower setting will not have an immediate effect. The
stored hot water will first have to be used. Additional checks of
the water temperature should follow completion of a cycle.
Further adjustments may be necessary as you use your BOILER
MATE™ and water piping system.

NOTE: VALVES FOR REDUCING POINT OF USE
TEMPERATURE BY MIXING COLD AND HOT WATER ARE
AVAILABLE. CONSULT A LICENSED PLUMBER OR THE
LOCAL PLUMBING AUTHORITY.

SEPARATE CIRCULATOR

ZONE VALVES - SCHEMATIC 3

3-WIRE ZONE VALVES

4-WIRE ZONE VALVES

PRIORITY W/CIRCULATORS - SCHEMATIC 4