Installation

10

Beijer Electronics, MAEN810C

3. Secure the operator panel in position, using all the fastening holes and the

provided brackets and screws:

4. Connect the cables in the specified order.

Use an M5 screw and a grounding conductor (as short as possible)
with a cross-section of minimum 2.5 mm

2

.

5. Carefully remove the laminated film over the operator panel display, to avoid

static electricity that could damage the panel.

x 7

0.5 - 1.0 Nm

B

C

D

A

Caution

Ensure that the operator panel and the controller system have the

same electrical grounding (reference voltage level), otherwise errors

in communication may occur.

Caution

- Use only shielded communication cables.

- Separate high voltage cables from signal and supply cables.

Caution

- The operator panel must be brought to ambient temperature

before it is started up. If condensation forms, ensure that the

operator panel is dry before connecting it to the power outlet.

- Ensure that the voltage and polarity of the power source is correct.

24V DC

RS422/

RS485
RS232

24V DC

A

D

Controller

Power

C

B

Ethernet